15
www.powershield.com.au
BF
Battery Fault
BV
Bypass Out Range
FU
Bypass frequency unstable
BR
Battery Replace
EE
EEPROM error
3-5. UPS Parameter Settings
Parameter 2 Parameter 3 Parameter 1
There are three parameters to set up the UPS.
Parameter 1: It’s for program alternatives. Refer to
below table.
Parameter 2&3: Its is the setting options or values
for program.
01: Output voltage setting
Interface
Setting
Parameter 2: Output voltage
For 200/208/220/230/240 VAC models, you may choose the
following output voltage:
200: presents output voltage is 200Vac
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac
240: presents output voltage is 240Vac (Default)
02: Frequency Converter enable/disable
Interface
Setting
Parameter 2: Enable or disable converter mode. You may
choose the following two options:
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
03: Output frequency setting
Interface
Setting
Parameter 2: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode is enabled, you may choose the following
output frequency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz