www.powershield.com.au 17
Fault code is shown as 14 and
the icon is lighting on
LCD display and alarm is
continuously sounding.
The UPS shut down
automatically because
short circuit occurs on the
UPS output.
Check output wiring and if
connected devices are in
short circuit status.
Fault code is shown as 01, 02,
03, 11, 12, 13 and 41 on LCD
display and alarm is
continuously sounding.
A UPS internal fault has
occurred. There are two
possible results:
1. The load is still
supplied, but directly
from AC power via
bypass.
2. The load is no longer
supplied by power.
Battery backup time is shorter
than nominal value
Batteries are not fully
charged
Charge the batteries for
at least 5 hours and then
check capacity. If the
problem still persists,
consult PowerShield.
Contact your dealer to
replace the battery.
The icon and the warning
code flashing on LCD
display and alarm is sounding
every 2 seconds.
Fan is locked or not
working
Check fans and notify
dealer!!
Fault code is shown as 45 on
LCD display. At the same time,
alarm is continuously sounding.
The charger does not have
output and battery voltage
is less than 10V/PC.