PQube 3 Not Locking on to Power Configuration
Your PQube 3 does not have an ON/OFF switch for recording data. It is designed to automatically
begin recording data as soon as it has locked onto the power configuration. If it cannot lock onto a
power configuration, it cannot record data and will blink orange.
If your PQube 3 is having trouble locking on, check the following:
You need to have at least 30 Vac applied between the L1 and N terminals or the L1 and L2 terminals.
Next, verify that you’ve connected the Earth conductor to your PQube 3. If you forget to install the
Earth conductor to your PQube 3, your PQube 3 may have problems locking onto the power
configuration. Connecting the Earth conductor is required to ensure the safety, reliability, and
accuracy of your PQube 3.