PQR
Series Model D52
Page 19
www.Powertronics.com
V2.1
Set Data Logger
The "Set Data Logger" menu item allows the
user to specify the device data logging rate, or
the time in between data log samples. The user
will be provided six choices: 1 second, 5
seconds, 10 seconds, 30 seconds, 1 minute, or 4
minutes. After selecting the desired logging
interval, pressing the "Okay" button will
instruct the program to set the device setting.
This process may take a few seconds.
When the rate is changed, the setting is NOT
saved in non-volatile RAM. The power up
default is one sample per minute.
Set Thresholds
The "Set Thresholds" menu item allows the user to
specify the thresholds at which the device will
trigger events. The user will be provided a dialog
box with input fields to specify the surge, sag, and
power failure thresholds for all available lines.
Entering zero will set the unit to test at 5% and 10%
limits. Entering a value between 1 and 999 will set
the actual voltage for the unit to trip at. Leaving a
field blank will keep the threshold set to its current
value. After specifying the desired settings, pressing
the "Okay" button will instruct the program to set
the device settings. This process may take a few
seconds