EasyManua.ls Logo

Powervar ACDEF2000-11 - Page 49

Default Icon
63 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
SPECIFICATIONS CONT.
SINERGY III UPS (200 - 240 Volt UPS’s) specifications cont.
Warranty/Support: Sinergy III Series products (hereafter referred to as “Product”) are warranted to be free from defects in material and work-
manship for two (2) years from date of shipment from POWERVAR, on the chassis & electronic components and two (2) years from date of
shipment from POWERVAR on the batteries. This warranty is limited to repairing, replacing, or refurbishing, at POWERVAR’s option, any defec-
tive component, circuit board or module within the Product. This warranty will include, at POWERVAR’s sole discretion, on-site service or
POWERVAR depot service. See the Limitations of Warranty section below for additional limitations & exclusions.
Battery Life Disclaimer
: POWERVAR’s standard battery warranty applies only to UPS and UPM products which are continuously connected to
AC mains power, except during utility power outages. Products which are regularly and intentionally disconnected from AC mains power will ex-
perience battery discharge/charge cycles potentially far more numerous than those for which the battery was designed. As a result, products used
in such applications will experience substantially reduced battery life. For that reason, POWERVAR’s standard battery warranty does not apply for
applications in which the UPS or UPM product is regularly and intentionally disconnected from AC mains power. POWERVAR UPS and UPM
products used in such applications shall receive a 90 day warranty on batteries.
POWERVAR, Inc. - 1450 Lakeside Drive, Waukegan, IL 60085
POWERVAR, Ltd. - Unit 5 Birch, Kembrey Park, Swindon, Wiltshire, UK SN2 8UU
Front Panel Controls
1. ON / MUTE - UP KEY (Previous Selection)
2. SELECT - DOWN KEY (Next Selection)
3. OFF / ENTER - CONFIRM KEY
Front Panel Display
Rear Panel Information and Controls
 6 Foot Detachable Line Cord with NEMA L6-20P
 (4) IEC320-C13 Direct
 (4) IEC320-C13 Programmable
 USB & RS-232 Communication
 SNMP Adapter (Optional)
 Internal Relay Contact Card (Optional)
 Circuit Breaker
Battery
Load
Input/
Output &
Battery
UPS
Status
Warning /
Fault Info
&
Setting
Operation
Backup
Time
Internal Batteries
 User Hot-Swappable (See Instruction Manual)
 Type - 12 V, 8.5 AH
 Quantity - 4 Batteries
 Recharge time - 12 Hours to 100%
Environmental
 Temperature: 0 to 40
0
C (32 to 104
0
F) Operating
-20 to 50
0
C (-40 to 122
0
F) Shipment,
Storage
 Humidity: <90% Non-Condensing (Operating,
Shipment, Storage)
 Altitude: <1000m Operating, No De-Rating
>1000m De-Rate Output 1% per 100m
Safety Agency and EMC Compliance
All units are listed by UL, and marked with the UL/cUL
marking.
Product Listings
 UL1778
 cUL to CSA22.2 No.107.1
Product Compliances
 FCC Part 15J Class A
 IEC61000-4-2, Electrostatic Discharge
 IEC61000-4-3, Radiated Electromagnetic Field Immunity
 IEC61000-4-4, Electrical Fast Transient/Burst Immunity
 IEC61000-4-5, Surge Immunity
 IEC61000-4-6, CS
 IEC61000-4-8, Power Frequency Magnetic Field
 IEC61000-2-2, Low Frequency Signal
 RoHS
11/2013 REV. D A03-00100