46
SPECIFICATIONS CONT.
SINERGY III UPS (200 - 240 Volt UPS’s) specifications cont.
Sinergy III Series UPS
3000 VA High Voltage
Model
Part Number
ACDEF3000-22
17302-01R
Type
Sinergy III
Power Rating
3000 VA / 2700 W
Topology
On-Line Double Conversion
Input Voltage (Nominal)
Range
200-240 VAC
180-300 VAC
Input Frequency
50/60 Hz ±4
(Auto Sense on Start-Up)
Input Power Factor
>0.95
Input Current THD
<9.0%
Efficiency
>86.0%
Output Voltage
208 VAC (Default)
200/220/230/240 VAC (Selectable)
Output Current
14.4 A (Default)
15.0/13.6/13.0/12.5 A (Selectable)
Voltage Regulation
±1.0%
Overload
Online Mode
100-105%: Continuous; Warning Only
105-130%: 2 Minutes
130-200%: 10 Seconds
>200%: 250 Milliseconds
Overload
Battery Mode
100-105%: Continuous; Warning Only
105-130%: 10 Seconds
>130%: 250 Milliseconds
Overload
Bypass Mode
100-110%: Continuous; Warning Only
110-120%: 30 Minutes
120-130%: 10 Minutes
>130%: 1 Minute
Battery Voltage (Float / Nominal)
82.1/72.0 VDC
Charger Current
1.0 A
Backup Time (Full Load)
>3.6 Minutes
Shipping Weight
83.0 lbs. / 37.7 kg.
Communications Interface
USB / RS-232
Heat Dissipation (BTU/Hour)
1500 at 100% Load
11/2013 REV. D A03-00101