30
3) Battery setting (available in all operational modes)
Interface Description
1. Dischg Protect :
Battery :
1.1
Enable : Battery discharge protection function is enabled. When the
DisChg Protect : UPS has been continuously operating in “battery/battery test mode”, the
Enable UPS will automatically shut down when the discharge time set by option
990 Minute 1.2 below has expired.
Batt Test Type : Disable : Battery discharge protection function is disabled.
Short Time :
1.2
Till Batt Low 0000 ~ 1500 : The maximum discharge time ranging from 0 to 1500 mi-
nutes. When “Dischg Protect” is enabled the UPS will shut down to
protect the battery after backup time arrives. If “Dischg protect” is dis-
Battery :
abled then this setting is not functional. The default value for this setting
is 990 minutes.
DisChg Protect :
2. Batt Test Type :
Enable 2.1 Short Time : Battery test will last for a duration of 10 seconds.
990 Minute 2.2 Long Time : The duration of the battery test can be set to 01 ~ 99
Batt Test Type : minutes.
Short Time : 2.3 Till Batt Low : Battery test will not stop until the battery voltage
10 Minute is low.
Battery :
DisChg Protect :
Enable
990 Minute
Batt Test Type :
Short Time :
10 Second