What does Err.23 mean on Powtran PI500-S 022G3 Inverter?
- DDustin ThompsonSep 23, 2025
If your Powtran Inverter displays Err.23, it indicates that the motor has a short to ground. Replace the cable or motor.

What does Err.23 mean on Powtran PI500-S 022G3 Inverter?
If your Powtran Inverter displays Err.23, it indicates that the motor has a short to ground. Replace the cable or motor.
What causes Err.03 on a Powtran PI500-S 022G3 and how to fix it?
The Err.03 error on your Powtran Inverter can arise from several factors. Here's what to check: * A short-circuit or earthing of the inverter output. If this is the case, eliminate peripheral faults. * If you're using vector control without identifying parameters, perform motor parameter identification. * A deceleration time that's too short. Increase the deceleration time. * Low voltage can cause this error. Set the voltage to the normal range. * If the load suddenly increases during deceleration, cancel the sudden load. * Lack of a braking unit and braking resistor. Install a braking unit and brake resistor.
Why does my Powtran PI500-S 022G3 show Err.04?
The Err.04 error on a Powtran Inverter can be attributed to the following reasons: * A short-circuit or earthing of the inverter output. If this occurs, eliminate peripheral faults. * If the control mode is vector and parameters haven't been identified, perform identification for the motor parameters. * Low voltage can trigger this error; set the voltage to the normal range. * A sudden increase in load during operation may also cause it; cancel the sudden load. * If the inverter type is too small, select an inverter with a larger power level.
What does Err.05 mean on my Powtran Inverter?
If your Powtran Inverter displays Err.05, consider the following potential causes and solutions: * If a braking unit and braking resistor haven't been installed, install them. * High input voltage can cause this error. Set the voltage to the normal range. * External force dragging the motor during acceleration can trigger this. Cancel the external force or install a braking resistor. * If the acceleration time is too short, increase it.
How do I fix Err.06 on my Powtran PI500-S 022G3?
If you're seeing Err.06 on your Powtran Inverter, here's what you should check: * High input voltage. Set the voltage to the normal range. * External force dragging the motor during deceleration. Cancel the external force or install a braking resistor. * A deceleration time that's too short. Increase the deceleration time. * Missing braking unit and braking resistor. Install a braking unit and brake resistor.
What does Err.22 mean on Powtran Inverter?
If your Powtran Inverter displays Err.22, it means there is an overvoltage or overcurrent. Eliminate the overvoltage or overcurrent fault.
What does Err.15 on Powtran PI500-S 022G3 Inverter mean?
If your Powtran Inverter is displaying Err.15, it means an external fault signal was input through the multi-function terminal DI. Reset run.
What does Err.21 mean on Powtran PI500-S 022G3 Inverter?
If your Powtran Inverter displays Err.21, it indicates that the EEPROM chip is damaged. Replace the main control panel.
What to do if Powtran Inverter shows Err.12?
If your Powtran Inverter displays Err.12, it could be due to: * An abnormal drive panel. Replace the drive, the power board or contactor. * An abnormal lightning protection plate. Seek technical support. * An abnormal main control panel. Check and eliminate the existing problems in the peripheral line.
What does it mean when my Powtran PI500-S 022G3 shows Err.11?
If your Powtran Inverter is displaying Err.11, consider these possibilities: * The power grid voltage might be too low. Check the power grid voltage. * The motor protection parameters (F8.03) might not be set appropriately. Correctly set this parameter. * The load could be too large, or the motor might be stalling. Reduce the load and check the motor and its mechanical condition.
Detailed safety warnings categorized by process (before installation, during installation, wiring, before energizing, during operation, maintenance).
Technical details including power, current, and adaptive motor ratings for various inverter models.
Guides for viewing/modifying parameters, reading status, password settings, and motor auto-tuning.
Details on suitable operating environment, installation direction, and required space.
Wiring descriptions for main and control circuits, along with essential wiring safety precautions.
Lists common fault codes, their possible causes, and recommended solutions for quick resolution.