23
PROGRAMMABLE TRANSMITTER 5114
Input for RTD, TC, mV, linear resistance, mA, and V
3-port 3.75 kVAC galvanic isolation
Current and voltage output
Universal voltage supply
1- and 2-channel versions
Loop supply > 17.1 V in Ex zone 0
APPLICATION
Electronic temperature measurement with resistance sensor or thermocouple
sensor. Ex barrier for temperature sensors, potentiometers, and current /
voltage signals Ex power supply for 2-wire transmitters in zone 0, 1, 2, 20, 21,
and 22. Amplification of mV signals. Conversion of linear resistance variation.
Galvanic isolation of analogue signals. Measurement of floating signals.
Linearisation of non-linear Ohm, mV, mA, or voltage signals. Separation of
circuits in PELV/SELV installations. The transmitter is especially suitable for
emitting the output current signal, either as a standard current signal or as a loop
signal.
TECHNICAL CHARACTERISTICS
The unit is based on a microprocessor core with an efficient program operation.
The basic calibration data and present set-up are stored in an EEPROM thereby
avoiding the loss or change of data at power off. The 2-channel version has a full
galvanic isolation between the channels. By way of jumpers on the PCB the input
in the standard version can be programmed either for a temperature or a current /
voltage input. This means that one channel can work as for instance a temperature
transmitter and the other can work as an isolation amplifier. Measurement range,
signal parameters, and output span are configured to the present task by way of a
PC and PR electronics A/S’ communica tions interface Loop Link.
INPUT TYPES
Temperature input - jumpers in position 1:
Thermocouple input (TC) for standard thermocouples type B, E, J, K, L, N, R,
S, T, U, W3, W5, LR according to the norms IEC 584, DIN 43710, ASTM E988-90
and GOST 3044-84. The CJC can be selected in 3 different ways: internally in
the terminal, externally by way of a Pt100 / Ni100 sensor, or externally with a
constant temperature.