9113 TEMPERATURE / mA CONVERTER Safety Manual
14.1.2 Parameters related only to Channel 2 (only for type 9113BB)
14.1.3. Parameters related to both channels
The above safety-related configuration parameters are marked in red
text in the routing diagrams and must be verified by the user in a SIL
configuration.
14.2. Verification procedure
The verification is done using the display / programming front PR 4501 and
following the procedure described below.
Name Function
CH1.TYP Functions as described for Channel 1 (14.1.1)
I.RANGE
CONNEC
UNIT
SENSOR
Pt.TYPE
Ni.TYPE
TC.TYPE
CJC
O.RANGE
OUT.ERR
OUT.LO
OUT.HI
RESP
USE.CAL
Name Function
NEW.PAS Password for protection of the device configuration from
un-authorized access. Range from 0 to 9999.