42
Holding Register (Analogue Output) Applicable Unit Type
Register Name Addr
Modicon
Address
Details
FTC4
FTC5
CAHV
master
CAHV
slave
CRHV
master
CRHV
slave
QAHV
master
EAHV
master
EAHV
slave
Heat Pump Slave 8 ON/OFF
(address 9 for CAHV/CRHV)
[READ ONLY]
135 40136 0 = Stop, 1 = Run
9
9
Heat Pump Run Time
(hours)
[READ ONLY]
136 40137
Value in hours
0 = 0 Hours … 99 = 99 Hours
9 9 9
9
Heat Pump Run Time
(hours x100)
[READ ONLY]
137 40138
Value in hours multiplied by 100
0 = 0 hours
…
65535 = 6553500 hours
9 9 9
9
Heat Pump Refrigerant Address
1 Run Time (hours x100)
[READ ONLY]
138 40139
Value in hours multiplied by 100
0 = 0 hours
…
65535 = 6553500 hours
9 9
Heat Pump Refrigerant Address
2 Run Time (hours x100)
[READ ONLY]
139 40140
Value in hours multiplied by 100
0 = 0 hours
…
65535 = 6553500 hours
9 9
Heat Pump Refrigerant Address
3 Run Time (hours x100)
[READ ONLY]
140 40141
Value in hours multiplied by 100
0 = 0 hours
…
65535 = 6553500 hours
9 9
Heat Pump Refrigerant Address
4 Run Time (hours x100)
[READ ONLY]
141 40142
Value in hours multiplied by 100
0 = 0 hours
…
65535 = 6553500 hours
9 9
Heat Pump Refrigerant Address
5 Run Time (hours x100)
[READ ONLY]
142 40143
Value in hours multiplied by 100
0 = 0 hours
…
65535 = 6553500 hours
9 9
Heat Pump Refrigerant Address
6 Run Time (hours x100)
[READ ONLY]
143 40144
Value in hours multiplied by 100
0 = 0 hours
…
65535 = 6553500 hours
9 9
Boiler ON/OFF
[READ ONLY]
144 40145
0 = Stop, 1 = Run
9 9
9 9
External Heater Operation 1
[READ ONLY]
0 = Stop, 1 = Run
9
9