13.1. Input registers
Input Registers are read using function code 04.
Input Register (Analogue Input) Applicable Unit Type
Register Name Addr
Modicon
Address
Details
Lossnay
LGH Series
MelcoBEMS MINI Firmware
Version
3 30004 MelcoBEMS MINI Firmware Version
9
Modbus Comms Counter 5 30006
Value of a counter which increments upon every
valid Modbus command received. Value will
automatically reset to zero when value exceeds
65535.
9
System Type Detected 9 30010
0 = ATA unit connected
1 = ATW system connected
2 = Lossnay system connected
255 = Undetermined (no unit detected yet)
9
Supply Air Temperature 174 30175
Temperature value in ºC multiplied by 10.
0 = 0ºC … 400 = 40ºC
Note: Only available when ‘Supply Air Temperature
Sensor’ value = 1 (Equipped).
Outdoor Temperature (signed) 175 30176
Temperature value in ºC multiplied by 10.
(see note *)
Note: Only available when ‘Outdoor Temperature
Sensor’ value = 1 (Equipped).
9
Outdoor Temperature 176 30177
Temperature value in ºC multiplied by 10.
(see note **)
Note: Only available when ‘Outdoor Temperature
Sensor’ value = 1 (Equipped).
9
Room Temperature A 177 30178
Temperature value in ºC multiplied by 10.
0 = 0ºC … 400 = 40ºC
Note: Only available when ‘Return Air Temperature
Sensor’ value = 1 (Equipped).
9