Input Register (Analogue Input) Applicable Unit Type
Register Name Addr
Modicon
Address
Details
Lossnay
LGH Series
Room CO2 Level 178 30179
CO2 level divided by 10.
0 = 0ppm … 240 = 2400 and above.
[Value 254 = Under detecting]
[Value 255 = No sensor]
Note: Only available when ‘CO2 Level Sensor’
value = 1 (Equipped).
Fault/Error Code (hex) 179 30180
0x8000 = No error
0x6999 = Bad communication with unit
(Refer to Lossnay unit documentation for
description of other fault code values)
9
Fault/Error Code (decimal) 180 30181
8000 = No error
6999 = Bad communication with unit
(Refer to Lossnay unit documentation for
description of other fault code values)
9
Energy Consumption 181 30182
Value in kWh multiplied by 10.
0 = 0kWh … 65535 = 6553.5kWh
9
Actual Operation Mode 182 30183
0 = Not auto mode
1 = Determining
2 = Heating
3 = Cooling
Actual Supply Fan Speed 183 30184
0 = Stop
1 = Speed 1
2 = Speed 2
3 = Speed 3
4 = Speed 4
9
Actual Extract Fan Speed 184 30185
0 = Stop
1 = Speed 1
2 = Speed 2
3 = Speed 3
4 = Speed 4
9
Minimum Cooling Setpoint 185 30186
Temperature value in ºC multiplied by 10.
0 = 0ºC … 400 = 40ºC
Note: Only available when ‘Set Temperature on
Temperature Control Unit’ value = 1 or 2.