Input Register (Analogue Input) Applicable Unit Type
Register Name Addr
Modicon
Address
Details
Lossnay
LGH Series
Maximum Cooling Setpoint 186 30187
Temperature value in ºC multiplied by 10.
0 = 0ºC … 400 = 40ºC
Note: Only available when ‘Set Temperature on
Temperature Control Unit’ value = 1 or 2.
Minimum Heating Setpoint 187 30188
Temperature value in ºC multiplied by 10.
0 = 0ºC … 400 = 40ºC
Note: Only available when ‘Set Temperature on
Temperature Control Unit’ value = 1 or 2.
Maximum Heating Setpoint 188 30189
Temperature value in ºC multiplied by 10.
0 = 0ºC … 400 = 40ºC
Note: Only available when ‘Set Temperature on
Temperature Control Unit’ value = 1 or 2.
Minimum Auto Setpoint 189 30190
Temperature value in ºC multiplied by 10.
0 = 0ºC … 400 = 40ºC
Note: Only available when ‘Set Temperature on
Temperature Control Unit’ value = 1 or 2.
Maximum Auto Setpoint 190 30191
Temperature value in ºC multiplied by 10.
0 = 0ºC … 400 = 40ºC
Note: Only available when ‘Set Temperature on
Temperature Control Unit’ value = 1 or 2.
Number of Fan Speeds 191 30192 Values 1 – 4 valid.
9
Set Temperature on
Temperature Control Unit
192 30193
0 = No set temperature display
1 = RA (Return Air) temperature
2 = SA (Supply Air) temperature