85
13.1. Coils
Coils are read using function code 01 and written to using either function code 05 or 15. Function code 05 is used when writing to a single coil register, function code 15 is
used for writing to multiple coil registers in the same command.
Coil (Digital Output) Applicable Unit Type
Register Name Addr
Modicon
Address
Details
Lossnay
LGH Series
Power On/Off 3 00004
0 = Power OFF
1 = Power ON
9
13.1. Discrete Inputs
Discrete Inputs are read using function code 02.
Discrete Input (Digital Input) Applicable Unit Type
Register Name Addr
Modicon
Address
Details
Lossnay
LGH Series
Thermo On/Off 80 10081
0 = Thermo OFF
1 = Thermo ON
Auto Fan Speed Control
Availability
81 10082
0 = Not available
1 = Available
Night Purge 82 10083
0 = Normal operation
1 = In night purge operation
During night-purge operation:
9