86
Discrete Input (Digital Input) Applicable Unit Type
Register Name Addr
Modicon
Address
Details
Lossnay
LGH Series
- Pressing ON/OFF button starts normal operation.
- When pressing the Ventilation button the Lossnay
remains in bypass mode
Maintenance Sign 83 10084
0 = Inactive
1 = Active
9
Filter Sign 84 10085
0 = Inactive
1 = Active
9
Actual Ventilation Mode 85 10086
0 = Lossnay ventilation
1 = Bypass ventilation
9
Setpoint 0.5ºC Increments
Availability
86 10087
0 = Not available
1 = Available
Heat/Cool or Cool-Only 87 10088
0 = Heat and Cool
1 = Cool only
Auto Operation Mode Availability 88 10089
0 = Not available
1 = Available
Heat/Cool or Heat-Only 89 10090
0 = Heat and Cool
1 = Heat only
Energy Consumption Data
Available
90 10091
0 = Not available
1 = Available
9
Bypass Damper Available 91 10092
0 = Not available
1 = Available
9
Auto Ventilation Mode Available 92 10093
0 = Not available
1 = Available
9
Operation Mode of Temperature
Control Unit
93 10094
0 = Not available (not connected)
1 = Available (connected)
Outdoor Temperature Sensor 94 10095
0 = Not equipped
1 = Equipped
9
Return Air Temperature Sensor 95 10096
0 = Not equipped
1 = Equipped
9