EasyManua.ls Logo

Progress Solar/Wind SLT 700 Series - Formerly RS-485)

Progress Solar/Wind SLT 700 Series
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
55TriStar MPPT Operators Manual
54
Networking and Communication
Serial Port Settings
Adjust the serial port settings as follows:
9600 BAUD
8 data bits
1 or 2 stop bits
no parity
The serial RS-232 connection provides a direct connection between a TriStar MPPT 150V and a PC
(or other serial device). Firmware updates can only be programmed through the RS-232 connec-
tion. The serial connection is not typically used for multi-controller networking. However, networking
is possible using a USB hub and USB-Serial cables. For more information, refer to the “Morningstar
Communications Document” at:
www.morningstarcorp.com/support
5.4 EIA-485 (formerly RS-485)
NOTE:
The EIA-485 connection is only available on the TS-MPPT-60/M model.
NOTE:
The RS-232 and EIA-485 ports share hardware. Both ports cannot be used simultaneously.
EIA-485 is a networking standard for serial communication between multiple devices on a bus. The
TriStar MPPT 150V communicates over an EIA-485 network via the open standard MODBUS
TM
proto-
col. Use EIA-485 networking to:
connect multiple TriStar MPPT 150V controllers on a network to log and view real-time
data using MSView
TM
PC software
program each controller on the network with custom charge settings using MSView
TM
PC
software
connect the TriStar MPPT 150V to other Morningstar controllers with the RSC-1 Serial to
EIA-485 Adapter (sold separately)
bridge an Ethernet connection through a TriStar MPPT 150V to an EIA-485 network
The EIA-485 port has four (4) connections: Power, Data A, Data B, and Ground. Data A & B are di󰀨er-
entially driven data lines that carry the network data. Power and Ground connections provide power
to the network. The TriStar MPPT 150V does not supply power to the EIA-485 network, therefore an
external power source is required. The source voltage must be between 8-16 Vdc. For 12 Volt sys-
tems, the network can be powered directly from the system battery. Use a DC-DC converter for 24,
36, and 48 Volt systems.
!
CAUTION: Equipment Damage
Tapping power o of individual batteries in a series string of batteries can cause a
voltage imbalance. Damage to the batteries may result. Always use a DC-DC converter
to power the EIA-485 network if the nominal system voltage is greater than 12 volts.
!
PRUDENCE : Endommagement de l’équipement
L’arrêt progressif de batteries individuelles dans une série de batteries peut provoquer
un déséquilibre de tension. Les batteries peuvent être endommagées. Utilisez toujours
un convertisseur CC-CC pour convertir l’alimentation au réseau EIA-485 si la tension
nominale du système est supérieure à 12 V.
For more information on EIA-485 networking, refer to the “Morningstar Communications Document”
on our website at:
morningstarcorp.com/support

Table of Contents