Setting Default Range Steps
Set alarm value (setting 33) 1% 0 - 100% 1%
Clear alarm value (setting 34) 1% 0 - 100% 1%
7.4.3. Low voltage alarm
When enabled, the alarm will activate when the battery voltage falls below the set value for more than 10 seconds. The alarm will
deactivate when the battery voltage rises above the clear value.
Setting Default Range Steps
Set alarm value (setting 35) 1.1V 0 - 95.0V 0.1V
Clear alarm value (setting 36) 1.0V 0 - 95.0V 0.1V
7.4.4. High voltage alarm
When enabled, the alarm will activate when the battery voltage rises above the set value for more than 10 seconds. The alarm
will deactivate when the battery voltage drops below the clear value.
Setting Default Range Steps
Set alarm value (setting 37) 1.1V 0 - 95.0V 0.1V
Clear alarm value (setting 38) 1.0V 0 - 95.0V 0.1V
7.4.5. Low starter voltage alarm
This setting is only available if the Aux input has been set to “Starter battery”, see chapter Aux input
[40].
When enabled, the alarm will activate when the starter battery voltage falls below the set value for more than 10 seconds. The
alarm will deactivate when the starter battery voltage rises above the clear value.
Setting Default Range Steps
Set alarm value (setting 39) 1.1V 0 - 95.0V 0.1V
Clear alarm value (setting 40) 1.0V 0 - 95.0V 0.1V