73TriStar MPPT Operators Manual
72
Specications
TriStar MPPT Voltage Drop Tables
Good system design generally requires large conductor wires that limit voltage drop losses to 2% or
less. The tables below provide wire sizing for a maximum of 2% voltage drop. Longer distance wire
runs may require signicantly larger wire sizes to reduce the voltage drop to an acceptable level.
2% Voltage Drop Chart for 75°C or 90ºC Stranded Copper Wire (Feet), 12 Volt System
Maximum 1-way Distance (feet), 12 Volt System - multiply values by (2) for 24 Volt and by (4) for 48V,
System.
Wire
Size
(AWG)
60A 55A 50A 45A 40A 35A 30A 25A 20A 15A
4/0
1
39.2 42.8 47.0 52.3 58.8 67.2 78.4 94.1 117.6 156.8
3/0
1
31.1 33.9 37.3 41.5 46.7 53.3 62.2 74.7 93.3 124.5
2/0
1
24.6 26.9 29.6 32.9 37.0 42.3 49.3 59.2 73.9 98.6
1/0 19.5 21.3 23.4 26.0 29.3 33.5 39.1 46.9 58.6 78.1
#1 15.5 16.9 18.6 20.6 23.2 26.5 31.0 37.1 46.4 61.9
#2 12.3 13.4 14.7 16.4 18.4 21.1 24.6 29.5 36.9 49.1
#3 9.7 10.6 11.7 13.0 14.6 16.7 19.5 23.3 29.2 38.9
#4 7.7 8.4 9.3 10.3 11.6 13.3 15.5 18.6 23.2 31.0
#6 4.9 5.3 5.8 6.5 7.3 8.3 9.7 11.6 14.6 19.4
#8 3.1 3.3 3.7 4.1 4.6 5.3 6.1 7.4 9.2 12.3
#10 2.9 3.3 3.8 4.6 5.8 7.7
#12 2.9 3.6 4.8
#14 2.3 3.0
1
Wires sizes larger than #2 AWG (35 mm
2
) must be terminated at a splicer block located
external to the TriStar MPPT. Use #2 AWG (35 mm
2
) or smaller wire to connect to the TriStar
MPPT to a splicer block.
Table A-3. Maximum 1-way wire distance for 12 Volt systems, stranded copper, 2% voltage drop
2% Voltage Drop Chart for 75°C or 90ºC Stranded Copper Wire (meters), 12 Volt System
Maximum 1-way Distance (meters), 12 Volt System - multiply values by (2) for 24 Volt and by (4) for
48V, System.
Wire
Size
(mm
2
)
60A 55A 50A 45A 40A 35A 30A 25A 20A 15A
120
1
12.7
13.9
15.3
17.0
19.1
21.8
25.5
30.6
38.2
51.0
95
1
10.1
11.0
12.1
13.5
15.2
17.4
20.2
24.3
30.4
40.5
70
1
7.3
8.0
8.8
9.8
11.0
12.6
14.7
17.6
22.0
29.4
50
5.1
5.5
6.1
6.8
7.6
8.7
10.2
12.2
15.3
20.3
35
3.8
4.1
4.5
5.0
5.6
6.4
7.5
9.0
11.3
15.0
25
2.7
3.0
3.3
3.6
4.1
4.6
5.4
6.5
8.1
10.8
16
1.7
1.9
2.1
2.3
2.6
2.9
3.4
4.1
5.2
6.9
10
1.3
1.4
1.6
1.8
2.2
2.6
3.2
4.3
6
1.3
1.5
1.9
2.6
4
1.0
1.3
1.7
2.5
0.8
1.1
1
Wires sizes larger than 35 mm
2
must be terminated at a splicer block located
external to the TriStar MPPT. Use 35 mm
2
or smaller wire to connect to the TriStar
MPPT to a splicer block.
Table A-4. Maximum 1-way wire distance for 12 Volt systems, stranded copper, 2% voltage drop