The secondary display "Signal current" indicates the incoming current.
You can select 5 types of current signal processing:
n
‘0 - 20 mA’
n
‘4 - 20 mA’
n
‘Linear curve ’
n
‘Lower side band’
n
‘Upper side band’
‘0 - 20 mA’
At 0 mA the pump is stationary –
At 20 mA the pump works at maximum stroke rate.
‘4 - 20 mA’
At 4 mA the pump is stationary –
At 20 mA the pump works at maximum stroke rate.
Curve
‘Linear curve’
The symbol "Linear curve" appears on the LCD screen. You can enter any
pump stroke rate behaviour proportional to the current signal. You can
enter the curve points I and F in the
‘Curve points’
menu. You define a
straight line here and thus the behaviour:
I [mA]
I 1
I 2
F1
F2
Fmax
0 20
P1
P2
B0088
Fig. 32: Frequency-current diagram for "Linear curve"
Plot a diagram similar to the one above – with values for
(I1, F1) and (I2, F2) – so that you can set the pump as
desired!
The smallest processable difference between I1 and I2
is 4 mA (ll I1-I2 ll ≥4 mA).
‘Lower side band’
‘Standard’
‘Extended’
Set up /
‘Menu’
49

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ProMinent Sigma 1 S1Cb and is the answer not in the manual?

ProMinent Sigma 1 S1Cb Specifications

General IconGeneral
BrandProMinent
ModelSigma 1 S1Cb
CategoryWater Pump
LanguageEnglish

Related product manuals