Heating
Temperature of the out-going
water in mode.
Range:
heating
15 to 40 °C
Default: 27 °C
Defrosting
Temperature to start the
DEFROST function.
Range: -30 to 0
Both conditions, i.e.
parameters 2 and 3 must be
fulfilled to start the
DEFROST mode.
°C
Default: -6 °C
Note:
Defrosting
Maximum time.
Range: 0 to 15 min
Default: 8 min
defrosting
If the unit is in the
defrosting mode the blue
DEFROST light on the
controller is on.
Note:
,
Cooling
Temperature of the out-going
water in cooling mode.
Range: 8 28to °C
Default: 27 °C
Defrosting
Running time of the com-
pressor after getting ice on
evaporator (energy collector).
Range: 30-90 sec
Default: 45 sec
Defrosting
Temperature
One of the conditions,
i.e. either parameter 4 or 5 is
enough to stop the DEFROST
mode.
to turn the
DEFROST function off.
Range: 0 to + 30 °C
Default: 13 °C
Note:
Not in use
Auto restart
Automatic restart after
power failure.
0 - no auto restarting
HP remains off.
1 - automatic restart of the
HP after power failure
Running mode
0-
Switch the mode by
pressing the MODE button.
This is possible only if “8” is
set to “1”. All other settings
can be changed only when
the pump is turned off.
cooling only
1 - cooling & heating
2 - not available
3 - heating only
Note:
15