5
Menu structure
5.1 "Info" menu
The Info menu shows the following readings and yield values:
Display
e.g.
Meaning
Can be
reset
75 °C Displays current collector temperature No
min
12 °C
Displays minimum collector temperature.
Can be reset to current temperature.
Yes
max
105 °C
Displays maximum collector temperature.
Can be reset to current temperature.
Yes
52 °C Displays current storage tank temperature No
min
40 °C
Displays minimum storage tank tempera-
ture. Can be reset to current temperature.
Yes
max
67 °C
Displays maximum storage tank tempera-
ture. Can be reset to current temperature.
Yes
25 °C
Displays S3 general temperature measuring
point (only shown if connected)
No
1234 h
Operating hours for charging storage tank
Can be reset to 0 h
Yes
5.2 "Programming" menu
The Programming menu is used to display operating parameters and to change
these as required. The preset values generally ensure fault-free system operation.
Display
e.g.
Meaning Value range
Typical
setting
Current
setting
max
65 °C
Storage tank:
Maximum permis-
sible temperature
15 – 95 °C 65 °C
dT max
7 K
Storage tank:
Switch-on dier-
ence
3 – 40K 7K
dT min
3 K
Storage tank:
Switch-o dier-
ence
2 – 35K 3K
min
100
Set minimum
pump capacity
using RPM con-
trol: 100% = RPM
control o
30% – 100% 100%
dT
1 K
Sets dT for the
dT-controlled
circulation when
using tube collec-
tors (K/sec)
1 – 5K 1K
The number of values
displayed depends on the
additional functions activated.