49
CO
2
accumulated
Float
Grams
Patent-pending table-based algorithm.
Also, see registers 131-133: Energy
accumulated since [date]
50
Earth current
Float
RMS Amps
A
rms10/12
51
L1-N voltage
fundamental
magnitude
Float
RMS Volts
For delta systems, the PQube calculates
a metering Neutral for this parameter.
52
L1-N voltage
fundamental
angle
Float
degrees
Range: ±180.0º
53
L2-N voltage
fundamental
magnitude
Float
RMS Volts
For delta systems, the PQube calculates
a metering Neutral for this parameter.
54
L2-N voltage
fundamental
angle
Float
degrees
Range: ±180.0º
55
L3-N voltage
fundamental
magnitude
Float
RMS Volts
For delta systems, the PQube calculates
a metering Neutral for this parameter.
56
L3-N voltage
fundamental
angle
Float
degrees
Range: ±180.0º
57
L1 current
fundamental
magnitude
Float
RMS Amps
58
L1 current
fundamental
angle
Float
degrees
Range: ±180.0º
59
L2 current
fundamental
magnitude
Float
RMS Amps
60
L2 current
fundamental
angle
Float
degrees
Range: ±180.0º
61
L3 current
fundamental
magnitude
Float
RMS Amps
62
L3 current
fundamental
angle
Float
degrees
Range: ±180.0º
63
Peak current
“since date
Integer
64
Peak power
“since date
Integer
65
Peak VA
“since date
Integer
66
Energy (Wh)
“since date
Integer
67
Battery installed
date
Integer
68
Analog Energy
(Wh) “since
date
Integer
69
PQube offset
from UTC
Float
Hours
Range -12.0 - +12.0 . Set by user in
Setup.ini file.
70
Harmonic L1-
N volts
Float
RMS Volts
Harmonic order specified in 166
71
Harmonic L2-
N volts
Float
RMS Volts
Harmonic order specified in 166
72
Harmonic L3-
N volts
Float
RMS Volts
Harmonic order specified in 166
73
Harmonic L1
current
Float
RMS Amps
Harmonic order specified in 166

Table of Contents