PQube User Manual 2.1
Page 76 of 113
194-195
L2 Voltage
THD
Float
Percent
196-197
L3 Voltage
THD
Float
Percent
198-199
L1 Current
TDD
Float
Percent
200-201
L2 Current
TDD
Float
Percent
202-203
L3 Current
TDD
Float
Percent
204-205
L1 Power
Float
Watts
206-207
L2 Power
Float
Watts
208-209
L3 Power
Float
Watts
210-211
L1 Apparent
Power (VA)
Float
VA
212-213
L2 Apparent
Power (VA)
Float
VA
214-215
L3 Apparent
Power (VA)
Float
VA
216-217
L1 volt-amps
reactive
Float
VAR
218-219
L2 volt-amps
reactive
Float
VAR
220-221
L3 volt-amps
reactive
Float
VAR
222-223
L1 True Power
Factor
Float
-
Value between -1.0 and +1.0
224-225
L2 True Power
Factor
Float
-
Value between -1.0 and +1.0
226-227
L3 True Power
Factor
Float
-
Value between -1.0 and +1.0
228-229
L2 Flicker P
inst
Float
-
Instantaneous value. For L1 see 72-
73
230-231
L3 Flicker P
inst
Float
-
Instantaneous value. For L1 see 72-
73
232-233
L2 Flicker P
ST
Float
-
10-minute value. For L1 see 74-75
234-235
L3 Flicker P
ST
Float
-
10-minute value. For L1 see 74-75
236-237
L2 Flicker P
LT
Float
-
2-hour value. For L1 see 76-77
238-239
L3 Flicker P
LT
Float
-
2-hour value. For L1 see 76-77
240-241
VARh
Float
VAR-hours accumulated since [date]
- shares this reset date with Energy,
see registers 131-133
242
DC Energy “since” date
Integer
Year
Typical values: 2009, 2010, etc.
243
DC Energy “since” date
Integer
Month
Range: 1 12
244
DC Energy “since” date
Integer
Day
Range: 1 31
245
Reset Energy Accumulators
Write-only
-
Set this register to 1 to reset the
energy accumulators in your PQube
246
Reset Analog Energy
Accumulators
Write-only
-
Set this register to 1 to reset the
analog energy accumulators in your
PQube