PQube User Manual 2.1
Page 79 of 113
Setup.ini Tags
Comments
Valid Values
Example
Time_Zone=
Enter the time zone where your PQube is
located. UTC sometimes called Greenwich Mean
Time (GMT)
Any combination
of 3 or 4 capital
letters
Offset_From_UTC_In_Hours=
Choose the number of hours your PQube should
add or subtract from UTC to calculate your local
time, if you are using SNTP protocol to set your
PQube’s time.
For example, the offset from UTC in Pacific
Standard Time is -8.
-12 to +13
Offset_From_UTC_In_H
ours=-8
UPS_Time_In_Minutes=
3
Specify how long your PQube stays on after
losing instrument power.
1 to 9
PQube_Primary_Language=
Sets the first language for the GIF output files
See Languages
folder for list of
valid languages
PQube_Secondary_Language=
Sets the secondary language for the GIF files
See Languages
folder for list of
valid languages
[Nominal_Inputs]
Nominal_Phase_To_Phase_Voltage=AUTO
Nominal_Phase_To_Neutral_Voltage=AUTO
By default, your PQube will automatically detect
your nominal voltage if it is one of the following:
Phase-Neutral
69V, 120V, 230V, 277V, 350V, or 400V
Phase-Phase
69V, 100V, 200V, 208V, 240V, 400V, 480V, 600V,
or 690V
If using Potential Transformers, you will need to
enter the nominal voltage multiplied by the ratio.
AUTO
Any number
between 50 to 400
for Phase-Neutral
Any number
between 50 to 690
for Phase-Phase
Nominal_Phase_To_Phase_
Voltage=
110
If using a 1000:1 Potential
Transformer:
Nominal_Phase_To_Phase_
Voltage=
110000