PQube User Manual 2.1
Page 80 of 113
Setup.ini Tags
Comments
Valid Values
Example
Nominal_Frequency=AUTO
By default, your PQube will automatically detect
your nominal frequency if it is 50, 60, or 400 Hz.
You can also manually set the frequency to 50,
60, or any frequency between 320 and 560Hz.
AUTO
50
60
Any number
between 320 to
560
[Recordings]
GIF_Graphs=ON
CSV_Files=ON
PQDIF_Files=OFF
Specify which file formats to save your
recordings in.
CSV files take the shortest amount of time to
process.
GIF files take a little longer to process.
PQDIF files take the longest time to process.
ON
OFF
Recorded_Samples_Per_Cycle=128
Event/Snapshot Waveform buffer contains 2048
samples. Reduce the sampling rate to increase
the number of cycles, or increase the sampling
rate to capture more detail.
NOTE:
If you turn on harmonic recording, your
sampling rate will automatically be set to 128
samples per cycle.
32
64
128
256
Event_RMS_Recording_Definition=Urms1/2
Urms1/2 is the overlapping single-cycle RMS
refreshed every half cycle, as defined in IEC
61000-4-30.
Urms1 is the non-overlapping single-cycle RMS,
which produces half as much data per second,
so the total time of the RMS graphs is doubled.
Urms1/2
Urms1
Capture_End_Of_Event=ON
Turning this setting OFF allows you to see up to
2048 samples at the beginning of an event, in
exchange for discarding the end of event data.
ON
OFF

Table of Contents