EasyManua.ls Logo

PSL PQube - Page 81

Default Icon
113 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PQube User Manual 2.1
Page 81 of 113
Setup.ini Tags
Comments
Valid Values
Example
Behavior_When_SD_Card_is_Full=DISCARD_OLDEST_MONTH
When the SD card becomes full, your PQube can
automatically delete the oldest month of data, or
you can choose to stop recording.
DISCARD_OLDEST_MONTH
STOP_RECORDING
Budeanu_VARs_Column_in_Event_CSV_Files=AUTO
Enable this option to show Budeanu VARs in
event CSV files. The AUTO setting turns this
value ON or OFF, depending if the Budeanu
calculation method is selected or not.
AUTO
ON
OFF
Fundamental_VARs_Column_in_Event_CSV_Files=
OFF
Enables Fundamental VARs in event CSV files.
Note that Fundamental VARs are calculated
based on 10/12 cycle data, not every cycle like
Budeanu VARs.
ON
OFF
[Channels]
Record_Phase_To_Phase_Channels=AUTO
Record_Phase_To_Neutral_Channels=AUTO
If your Power Configuration includes a neutral
conductor, your PQube will automatically be set
to record Phase-Neutral channels.
If your Power Configuration includes multiple
phases, it will automatically record Phase-Phase
channels.
AUTO
ON
OFF
Record_AN1_E_Channel=AUTO
Record_AN2_E_Channel=AUTO
Record_AN1_AN2_Channel=AUTO
Record_DIG1_Channel=AUTO
The AUTO setting records the Analog and Digital
Input channels if Events are enabled on these
channels.
AUTO
ON
OFF
Record_Flicker=ON
Record_Voltage_THD=ON
Record_Current_TDD=ON
Record_Voltage_Unbalance=ON
Record_Current_Unbalance=ON
ON
OFF

Table of Contents