PQube User Manual 2.1
Page 94 of 113
Probe_2_High_Humidity_Events=OFF
Probe_2_Low_Humidity_Events="OFF"
Probe_2_Low_Humidity_Threshold_in_Percent_RH=0
Probe_2_High_Humidity_Threshold_in_Percent_RH=1
00
Probe_2_Humidity_Event_Hysteresis_in_Percent_RH=
2
[Event_Relay_Trigger]
Trigger_Relay_On_Dip=OFF
Trigger_Relay_On_Major_Dip=OFF
Trigger_Relay_On_Swell= OFF
Trigger_Relay_On_Interruption= OFF
Trigger_Relay_On_AN1_Dip= OFF
Trigger_Relay_On_AN1_Swell= OFF
Trigger_Relay_On_AN2_Dip= OFF
Trigger_Relay_On_AN2_Swell= OFF
Trigger_Relay_On_AN1_AN2_Dip= OFF
Trigger_Relay_On_AN1_AN2_Swell= OFF
Trigger_Relay_On_DIG1_Dip= OFF
Trigger_Relay_On_DIG1_Swell= OFF
Trigger_Relay_On_Underfrequency= OFF
Trigger_Relay_On_Overfrequency= OFF
Trigger_Relay_On_Impulse= OFF
Trigger_Relay_On_Snapshot= OFF
Trigger_Relay_On_Waveshape_Change= OFF
Your PQube triggers for many types of events. You
can choose which of these events will open one or
more relays. Each relay will remain open for 3
seconds or the event duration, whichever is longer.
Here are a few simple rules:
You can connect any event to any relay.
One relay may be connected to multiple
events, and any event can be connected to
multiple relays.
RLY1 is standard. RLY2, RLY3, and RLY4 are
included in the factory-installed RLY option.
Enter 1, 2, 3, 4 (or any combination of those
numbers) into the relay-eventtags to attach that
relay to that event.
Enter OFF if you don’t want that event to
trigger a relay.
OFF
1
2
3
4
Trigger_Relay_On_Dip=1
Trigger_Relay_On_Major_Dip=3
Trigger_Relay_On_Swell=24
Trigger_Relay_On_Interruption=1234