PQube User Manual 2.1
Page 94 of 113
Probe_2_High_Humidity_Events=OFF
Probe_2_Low_Humidity_Events="OFF"
Probe_2_Low_Humidity_Threshold_in_Percent_RH=0
Probe_2_High_Humidity_Threshold_in_Percent_RH=1
00
Probe_2_Humidity_Event_Hysteresis_in_Percent_RH=
2
Trigger_Relay_On_Dip=OFF
Trigger_Relay_On_Major_Dip=OFF
Trigger_Relay_On_Swell= OFF
Trigger_Relay_On_Interruption= OFF
Trigger_Relay_On_AN1_Dip= OFF
Trigger_Relay_On_AN1_Swell= OFF
Trigger_Relay_On_AN2_Dip= OFF
Trigger_Relay_On_AN2_Swell= OFF
Trigger_Relay_On_AN1_AN2_Dip= OFF
Trigger_Relay_On_AN1_AN2_Swell= OFF
Trigger_Relay_On_DIG1_Dip= OFF
Trigger_Relay_On_DIG1_Swell= OFF
Trigger_Relay_On_Underfrequency= OFF
Trigger_Relay_On_Overfrequency= OFF
Trigger_Relay_On_Impulse= OFF
Trigger_Relay_On_Snapshot= OFF
Trigger_Relay_On_Waveshape_Change= OFF
Your PQube triggers for many types of events. You
can choose which of these events will open one or
more relays. Each relay will remain open for 3
seconds or the event duration, whichever is longer.
Here are a few simple rules:
• You can connect any event to any relay.
• One relay may be connected to multiple
events, and any event can be connected to
multiple relays.
• RLY1 is standard. RLY2, RLY3, and RLY4 are
included in the factory-installed RLY option.
• Enter 1, 2, 3, 4 (or any combination of those
numbers) into the relay-eventtags to attach that
relay to that event.
• Enter OFF if you don’t want that event to
trigger a relay.
Trigger_Relay_On_Dip=1
Trigger_Relay_On_Major_Dip=3
Trigger_Relay_On_Swell=24
Trigger_Relay_On_Interruption=1234