Inlet Filters
The Inlet Filters should be checked and cleaned as necessary every 12 months.
Note! The Inlet Filters must not be removed except for cleaning. If the Thermostatic
Mixer is operated without the Inlet Filters tted the Warranty on the product will be
void.
Exposed Models
1. Isolate the hot and cold water supplies and operate the control lever to drain
any residual water.
2. Carefully unscrew the lter caps and remove the lters.
3. Clean the lters under a jet of water to remove any lodged particles.
4. Ret the lters and tighten the lter caps.
Note! Make sure that the ‘O’ seal is tted correctly and not damaged.
5. Turn on the hot and cold water supplies and check for leaks.