Product specific information for use with floorheating
systems
Use with T2QuickNet:
The T2QuickNet product line is approved with the
thermostat working in floor sensor mode. Be aware that
the floor sensor must be installed and activated for an
installation with T2QuickNet.
Use with T2Red (T2Reflecta) self-regulating systems:
Self-regulating heating cables have an inrush current
at start up. In order to guarantee the life time of the
thermostat, the maximum load of the self-regulating
application in nominal conditions is limited to 10A.
A 13A self-regulating load will reduce the life time of the
relay contacts.
Direct, connection e.g. single heating circuit
Remote set
back signal
Power supply
230 VAC
Floor
sensor
FP
L
N
10K
NTC
PE
SENSOR
N
L
N
L
L
N
PE
PE
Heating cable
230 VAC
Max.13A