17
New offset =
T
menu 1 -
T
surface
Example: Use the floor sensor temperature value from menu
1. If this value is 27°C and the floor surface thermometer
shows 24°C, the new offset value will be 27-24 = 3.
Change the offset from 4°C to 3°C.
Push confirmation button several times (scroll through
Menu structure) for leaving the Calibration mode to Normal
mode
4.3.3 Menu 3: Delayed Start-Up
The user can choose the time before powering up the floor
warming system.
Possible values: from 0 [OFF] to 15 minutes [15 ’]. A "t"
is shown on in the display when the delayed start-up is
switched on.
4.3.4 Menu 4: First warming function
Possible values: [OFF] or [ON]
This function does not apply by default (Installer menu
number 4: OFF by default, factory value = OFF).
T
surface
T
menu1
+
+