EasyManuals Logo

RCS TZ43 User Manual

RCS TZ43
37 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background imageLoading...
Page #24 background image
DCN 141-01128-04 10/6/08
24
Minimum Off Time Range: 5-9 Minutes Default: 6
Sets the minimum off time before another heating/cooling cycle can begin. Provides compressor short
cycle protection.
Fan Cycler Submenu
The fan cycler function cycles the HVAC system fan for an ON period followed by an Off period
continuously. Used to provide minimum air ventilation requirements. When the Fan ON time is
set to a value greater than 0, an additional “Cycler” FAN mode is present when pressing the FAN
button.
Fan ON Time Range: 0-120 minutes Default: 0 (=OFF)
Fan OFF Time Range: 0-120 minutes Default: 20
Remote Sensors Submenu
The TZ43 can support 2 remote sensors, 10K Thermistor type. Each sensor can support several
“Thermostat Curves”, the most common curves being the A-Curve, Type 2 and Type 3.
RS1 Type Range: A Curve, Type 2, Type 3 Default: Type 2
Selects the 10K Thermistor curve for Remote Sensor 1. If present, Remote Sensor 1 will replace
the internal sensor of the TZ43 and become the Primary temperature sensor.
RS2 Type Range: A Curve, Type 2, Type 3 Default: Type 2
Selects the 10K Thermistor curve for Remote Sensor 2. If present, Remote Sensor 2 will be
averaged with the Primary sensor (either the internal or RS1). Optionally RS2 can be configured
to be an Outdoor sensor (see RS2 Location).
RS2 Location Range: In or Out Default: In
RS2 can optionally be configured as an Outdoor sensor.
Zwave Install Button Submenu
Used to install/un-install the TZ43 into a Zwave Network.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RCS TZ43 and is the answer not in the manual?

RCS TZ43 Specifications

General IconGeneral
BrandRCS
ModelTZ43
CategoryThermostat
LanguageEnglish

Related product manuals