REFU Elektronik GmbH REFUsol 08K ... 23K 43
• Power-up time
• K factor (fault ride through)
REFUset
can be downloaded from www.refu.com.
6.5
Communication via Ethernet
The settings for the Ethernet communication can take place either manually or automatically (via DHCP).
Manually is the default setting.
6.5.1
Automatic Setting via DHCP
1. Navigate to Menu
Configuration > Communication > Ethernet > DHCP
.
2. Enter “1” in DHCP input field.
3. Press
OK
to confirm.
4. Restart inverter by opening and re-closing the DC switch.
The settings for IP address, subnet mask, standard gateway and DNS are automatically taken from
the DHCP server, e.g. the router.
6.5.2
Manual Setting
In order to ensure a trouble-free operation, all values must be given by the responsible network
administrator and individually set in each inverter.
1. Navigate to
Configuration > Communication > Ethernet > IP address
.
2. Enter IPv4 address. The IPv4 address is arbitrary, but must be consistent throughout the subnet.
Default value:
192.168.130.30
3. Press
OK
to confirm.
4. Navigate to
Configuration > Communication > Ethernet > Subnet mask
.
5. Enter IPv4 mask. The IPv4 mask is arbitrary, but must be consistent throughout the subnet Default
value:
255.255.0.0
6. Press
OK
to confirm.
7. Navigate to
Configuration > Communication > Ethernet > Standard gateway
.
8. Enter the address of the router that allows connection to the internet
Default value:
192.168.1.1
9. Press
OK
to confirm.
10. Navigate to
Configuration > Communication > Ethernet > DNS
.
11. Enter arbitrary IPv4 address of the superior DNS server
Default value:
0.0.0.0
12. Press
OK
to confirm.
13. Restart inverter.