Troubleshooting 51
Error List
REFUsol 100K
982059/02
2020-11
EnglishDeutsch
11 Troubleshooting
11.1 Error List
Error Code Message Description Instructions
11005
Isolation Error An insulation fault was detected during the
self-test before grid connection.
Check measured value and limit value in
REFUset.
Check the installation of the inverter.
Check PE connection.
Check for faulty cables (e.g. damaged insu-
lation).
Check solar generator installation.
70004
Safety Relay Broken The self-test of the safety relays could not be
completed successfully.
Open and close the DC switch.
If this error occurs more than once, contact
REFU Service.
70005
Relay Test Bad Comm1 The self-test of the safety relays detected a
communication problem.
70006
Relay Test Bad Comm2
70007
Relay Test Bad Comm3
70008
Relay Test Bad Comm4