Troubleshooting 63
Error List
REFUsol 100K
982059/02
2020-11
EnglishDeutsch
A0196
DC voltage too high The unit was shut down after the DC input
voltage exceeded the unit's rated voltage.
▸Measure DC voltage.
▸Set the DC voltage value indicated on the
type label.
▸Acknowledge the error.
A0197
DC Overvoltage DC overvoltage occurred.
▸Measure DC voltage.
▸Set the DC voltage value indicated on the
type label.
A0198
DC asymmetry DC voltage unbalanced. No action necessary.
A0199
DC voltage jump An unacceptable DC voltage peak has occur-
red. The unit is in a safe mode for a short time
to prevent damage to property.
No action necessary.
A019A
DC part timeout Timeout in DC part component monitoring oc-
curred.
No action necessary.
▸If the error still occurs, contact REFU Ser-
vice.
Error Code Message Description Instructions