Manual CORRIGO C-SERIES 2000.09
7. Stop on alarm from rotating heat exchanger
An alarm from a rotating heat exchanger can initiate a complete stop of the
unit.
This to prevent running at too low a temperature. Heat exchanger
malfunction can also lead to unneccessarily high running costs which is
avoided by stopping the unit when an alarm is indicated on input DI4.
The function is only available if rotating heat exchanger has been configured.
Alarms -Overview
Operational failure Supply air fan AI1
Operational failure Exhaust air fan AI2
Operational failure, pump DI2 With water heater
Frost protection AI8 With water heater
High temperature limit AI8 With electric heater
Fire alarm DI5
Fire damper DI6
Rotation sentinel, heat exchanger DI4
Chiller DI3
External alarm DI6 When DI6 is configured
for external alarm
Sensor failure AI3-AI8
Temperature deviation
Pressure deviation
Output in manual mode
Manual running mode
Switch not in Auto mode DI6 When DI6 is configured
for this, external switch.
Stop Exch alarmá
No