EasyManuals Logo

Regin Corrigo C Series User Manual

Regin Corrigo C Series
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #48 background imageLoading...
Page #48 background image
49
Manual CORRIGO C-SERIES 2000.09
CONFIGURATION- Corrigo C10 M N O P . Q R S
Configuration code 2 . 0
M Function DI6/DO6
0. External alarm & frost protection 0
1. Auto position & frost protection 1
2. Fire damper exercising
N Fire alarm
0. Alarm only 0
1. Alarm + supply air and exhaust air fans stop 1
2. Alarm + supply air fan stops 2
3. Alarm + exhaust air fan stops 3
O Function DI7/DI8
0. Not active 0
1. Pushbutton 1
2. Timer 2
P 2-speed fans (Can not be combined with DX-cooling)
0. No 0
1. Yes 1
Q External setpoint
0. No 0
1. Yes 1
R Daylight saving time
0. No 0
1. Yes 1
S This function is not available for Corrigo C10
The code must always be set to 0 0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Regin Corrigo C Series and is the answer not in the manual?

Regin Corrigo C Series Specifications

General IconGeneral
BrandRegin
ModelCorrigo C Series
CategoryController
LanguageEnglish

Related product manuals