51
Manual CORRIGO C-SERIES 2000.09
CONFIGURATION- Corrigo C20 MN O P . Q R S
Configuration code 2 0 . 0
M Function DI6/DO6
0. External alarm & frost protection 0
1. Auto position & frost protection 1
2. Fire damper exercising
N Fire alarm
0. Alarm only 0
1. Alarm + supply air and exhaust air fans stop 1
2. Alarm + supply air fan stops 2
3. Alarm + exhaust air fan stops 3
O Function DI7/DI8
0. Not active 0
1. Pushbutton 1
2. Timer 2
P Function not available for Corrigo C20
This code must always be set to 0 0
Q External setpoint
0. No 0
1. Yes 1
R Daylight saving time
0. No 0
1. Yes 1
S This function is not available for Corrigo C20
The code must always be set to 0 0