Regio Midi manual Chapter 4 Technical data 11
Models with display
Display type ......................................................................... LCD with background illumination
EMC emission and immunity standard
This product conforms to the requirements of the EMC Directive 2014/35/EU through product
standards EN 61000-6-1 and EN 61000-6-3.
RoHS
This product conforms to the Directive 2011/65/EU of the European Parliament and of the
Council.
Inputs
AI1 ........................................................................... PT1000-sensor, 0...50°C, accuracy ± 0.1°C
UI .....................................................................AI: PT1000-sensor, 0...100°C, accuracy ± 0.2°C
............................................................................................................................ or AI2: 0…10 V
....................................................................................................................... or DI: see DI below
CI .................................................................................... Regin’s condensation sensor, KG-A/1
DI ..................................................... Closing potential-free contact connected to +C in one end
Outputs
DO ............................................................................................................... 24 V AC, max 0.5 A
UO ..................................................... DO:24 V AC, max 2.0 A or AO:0...10 V DC, max 5 mA
+C, power output for DI only .............................. 24 V DC, max 10mA, short circuit protected
For more information about inputs and outputs, see the chapter Wiring.
Accessories for Regio Midi
External temperature sensors ........................ TG-R5/PT1000,TG-UH/PT1000,TG-A1/PT1000
Occupancy detector .......................................................................................................... IR24-P
Relay module for -F-models .................................................................................................. RB3
Change-over .........................................................................................................TG-A1/PT1000
Condensation sensor ........................................................................................................ KG-A/1
CO
2
transmitter ................................................................................................................ CO2RT
Service adapter for Regio Midi ................................................................................... RC-TEST
Connection plates ................................................................................................... RC-CONN:10
The accessories are available from Regin. For more information, see the product sheets and
instructions for each product, search via www.regincontrols.com.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Regin Regio Midi and is the answer not in the manual?

Regin Regio Midi Specifications

General IconGeneral
BrandRegin
ModelRegio Midi
CategoryController
LanguageEnglish

Related product manuals