7
Getting Started
USER GUIDE
MACH-PROCOM/MACH-PROWEBCOM
MACH-PROCOM
™
/MACH-PROWEBCOM
™
2007 − 2015 Reliable Controls
®
Corporation. All rights reserved.
MACH-PRO(WEB)COM SOFTWARE FEATURES
The MACH-Pro(Web)Com controller’s onboard memory allows for the creation of a total of
2040 BACnet objects.
Each object type is limited to the following maximums:
The MACH-Pro(Web)Com can communicate with up to 128 Modbus slaves and each one
counts as an object. Multipoint and Single-Point Trend Logs are dynamically created but
also count towards the 2040 object maximum.
The MACH-ProCom can support a maximum of 1536 Net-Ins (object updates from other
BACnet devices), and 512 Net-Outs (writing to objects in other BACnet devices or sending
object updates to other BACnet devices).
The entire MACH-Pro(Web)Com database is maintained in non-volatile Flash memory.
Items that dynamically change, such as Trend Logs and calculated values, are also
preserved in capacitor-backed memory. This feature retains values for power outages up
to 72 hours.
• 192 inputs.
• 128 outputs.
• 1,024 variables with standard and custom ranges available.
• 128 PID Loops for closed loop control.
• 128 Schedules.
• 32 Calendars.
• 128 Arrays (128 elements each).
• 20 Custom Tables for creating custom Input ranges.
• 64 System Groups of up to 160 points per group display.
• 128 Control-BASIC programs, each with 3200 bytes.
• 128 user passwords (Does not count towards the 2040 object maximum).
• 24 Custom Units – eight binary, eight analog, and eight multistate engineering
units (Does not count towards the 2040 object maximum).
• 16 SMART-Sensors.
• BACnet alarms can be emailed from the controller as dictated by the BACnet
Alarm Configuration setup.