What to do if the temperature of the heat exchanger is too low in my REMEHA Quinta Pro 30?
- JJeanette SwansonAug 31, 2025
If the temperature of the heat exchanger is too low in your REMEHA Boiler, check the wiring and ensure the sensors are operating correctly and that the sensor has been fitted properly. Replace the sensor if necessary. Also, vent the air from the CH system, check the circulation (direction, pump, valves), check the water pressure and the cleanliness of the heat exchanger. If present, check the boiler type parameter setting.