C
cynthia26Aug 29, 2025
Why does REMEHA Boiler have maximum difference between the flow and return temperature exceeded?
- JJoshua SharpAug 30, 2025
If the maximum difference between the flow and return temperature is exceeded in your REMEHA boiler, it could be due to no flow or insufficient flow, or a sensor error. Check the flow (direction, pump, valves), the water pressure, that the sensors are operating correctly, that the sensor has been fitted properly, and the cleanliness of the heat exchanger.