© RESOL 04272 deltasol_bs.mon.pmd
| 16
For control and service work the operating mode of the
controller can be manually adjusted by selecting the
adjustment value MM, in which the following adjustments
can be made:
4.1.18 Operating mode
• HND1 / HND2
Operating mode
OFF : relay off (flashing) +
AUTO : relay in automatic operation
ON : relay on (flashing) +
HAND / HND1 / HND2:
BOperating mode
Adjustment range:
OFF, AUTO, ON
Factory setting: AUTO
4.1.17 Pump speed control
A relative minimum pump speed is specified for pumps
connected at the outputs R1 and R2 via adjustment
channel nMN.
Attention:
When using consumers (e.g. valves) which are not
pump speed controlled, the value must be
adjusted to 100 % in order to deactivate the pump
speed control.
nMN:
Pump speed control
Adjustment range:
30 ... 100
Factory setting: 30
(PG 67.30 and PG 69.30)
4.1.19 Language
The menu language can be adjusted in this channel.
• dE : German
• En : English
LANG:
Adjustment of language
Adjustment range: dE, En
Factory setting: dE