2.1.2 Signal Connection
The following requirements apply for the signal connection wiring:
● flexible cables with wire end sleeves
● cable cross-section: 0.3...1.0 mm
2
● cable length: max. 20 m
● analog inputs ±10 V, VR1, VR2, +I and GND: use shielded cables
● analog inputs +I and GND: to eliminate interference from external influences,
connect +I and GND on the transducer with a 22 nF capacitor (50 V) and run
the signal cable two or three times through a ferrite ring.