Form CP-MAPSIII-D21, Doc No 303070, Page 33
BMS Cong Eh6 BMS Cong Screen Eh6 will be shown when the BMS Protocol is set to BACnet IP/Eth
Name Description Default Unit Min Max
DNS 1: Sets DNS 1 - [0-255] [0-255] [0-255] [0-255]
DNS 2: Sets DNS 1 - [0-255] [0-255] [0-255] [0-255]
Type: Sets the Type IP/Eth
BMS Cong Eh7 BMS Cong Screen Eh7 will be shown when the BMS Protocol is set to BacNet MSTP or BACnet IP/Eth
Name Description Default Unit Min Max
Function: Sets Function - Read or Write Read
Update: Sets Update - Yes or No Yes
BMS Cong Eh8 BMS Cong Screen Eh8
Name Description Default Unit Min Max
OA_Hum_Sel:
Share OA Humidity from BMS (0=Probe, 1=BMS) - Set value to BMS for OA humidity share
from BMS
Probe Probe BMS
OA_Temp_Sel:
Share OA Temp from BMS (0=Probe, 1=BMS) - Set value to BMS for OA temp share from
BMS
Probe
Probe BMS
Occupied_BMS
Occupied Mode BMS - Used to determine unit occupancy when OccMode_Sel is set to
BMS
Occ Occ
Un-
occ
Main Menu
F Factory Settings Factory Settings Menu is password protected Consult factory for access