Time Clock/Fireman’s Switch
To operate the heater with a time clock, connect the timer
   
The time clock should be of the dual switch type and set to
󰀨


digital control board. Splice into the red wire jumper tagged

      
must be a dry contact and must not supply power to the

may damage the heater, and is not covered by warranty.


NOTE: When using a time clock, the heater will display

󰀨
High Limits
The heater is equipped with two automatic high limits. Both
are located in the inlet/outlet header. Both are set to open

NOTE: An erratic high limit is often characteristic of
an internal heat exchanger problem, e.g. scale build-up,
     
page 41).
High Limit Removal
 Shut off main electrical power switch to heater.
 Remove front door.
 Remove defective high limit and replace with a new
high limit.
 Replace inspection panel.
Figure 38. High Limit
Flow Switch

󰀨

Figure 39. Flow Switch
Blocked Vent Switch
This heater is equipped with a blocked vent pressure
switch to prevent the operation of the heater when the vent
is blocked.
Figure 40. Blocked Vent Switch
Adjusting Valve Manifold Pressure
 Gas manifold pressure is measured at the pressure
tap between the gas valve and gas orifice (See
Figure 40).
 To increase the manifold pressure and increase
the ratio of fuel to air turn the adjustment screw
     Figure 33).
   
      
adjustment screw counterclockwise. Increasing
manifold pressure will increase the CO percentage
in the flue gases.
 To decrease the manifold pressure and decrease the
ratio of fuel to air turn the adjustment screw clockwise
Figure 41). Decreasing manifold
pressure will reduce the CO percentage in the flue
gases.
NOTE: Manifold pressure will decrease when the intake

     

APPROVED
UNCONTROLLED DOCUMENT IF PRINTED