0MNMHEM30RUENUB 00 pag. 55 / 57
400Vca 3-phase + N (configurable from 380V to 415V)
± 20% (adjustable from ± 5% to ± 25% from control
panel)
50 or 60Hz (auto-sensing)
± 2% ( ±1 ÷ ± 6% from control panel)
Switching onto bypass with synchronized
Inverter (UPS in “Normal Mode”)
Switching onto bypass with Inverter out of sync
(UPS in “Normal Mode”)
Switching from bypass to Inverter (UPS in
“Stand-by On mode”)
Delay in transfer onto Inverter after switching
onto bypass
Power overload capacity of the bypass line
110 % for 60 minutes, 125 % for 10 minutes, 150 % for 1
minute
i²t SCR bypass (8÷10ms) [A²s]
25°C
125°C
Short circuit capacity of the bypass line (x rated
current)
1 second
500 ms
200 ms
100 ms
10 ms