Operation, indication, diagnostics
43
20051011
7.5.3 First start-up with a new program module or in
case of replacement of program module
Tab. AA
Display shows alternately rSt and PrC.
Display shows the replacement of the program module.
Signal lamp blinks red once and yellow twice alternately.
Press for >3 seconds to start data download from the program module.
Signal lamp blinks yellow.
The process of 3 seconds is supported by a short flash of the yellow signal lamp.
Note:
If you press for <3 seconds, data download does not start. To start the restore process again, the
LME7... must be reset by switching mains ON/OFF.
Display shows run during download (restore process) of the program sequence.
Display shows alternately End and rSt.
Display shows the end of data exchange.
After 2 minutes, the unit changes to Loc 138
After the restore process, the unit is automatically in the lockout position (LOC 138) and must be reset for
operation!
Press for >1 second to reset the unit.
Display: OFF
nfo
nfo
nfo
On first startup or after exchange of the pro-
gram module, the sequence of functions and
parameter settings must be checked upon com-
pletion of the restore process.