6.2 OPERATING IRREGULARITIES
7. SAFETY WARNINGS
The dimension of the boiler’s combustion chamber must respond to specific values, in order to guarantee a
combustion with the lowest polluting emissions rate.
The Technical Service Personnel will be glad to give you all the imformation for a correct matching of this
burner to the boiler.
This burner must only be used for the application it was designed for.
The manufacturer accepts no liability within or without the contract for any damage caused to people, ani-
mals and property due to installation, adjustment and maintenance errors or to improper use.
7.1 BURNER IDENTIFICATION
The Identification Plate on the product gives the serial number, model and main technical and performance
data. If the Identification Plate is tampered with, removed or missing, the product cannot be clearly identi-
fied thus making any installation or maintenance work potentially dangerous.
7.2 BASIC SAFETY RULES
Children or inexpert persons must not use the appliance.
Under no circumstances must the intake grids, dissipation grids and ventilation vents in the installation
room be covered up with cloths, paper or any other material.
Unauthorised persons must not attempt to repair the appliance.
It is dangerous to pull or twist the electric leads.
Cleaning operations must not be performed if the appliance is not disconnected from the main power
supply.
Do not clean the burner or its parts with inflammable substances (e.g. petrol, alcohol, etc.). The cover
must be cleaned with soapy water.
Do not place anything on the burner.
Do not block or reduce the size of the ventilation vents in the installation room.
Do not leave containers and inflammable products in the installation room.
FAULTS POSSIBLE CAUSES SOLUTION
The burner locks out
during operation.
Earth probe.
Check the right position and if necessary
set it according to the instructions of this
manual.
Clean or replace the ionization probe.
The flame disappears 4 times.
Check the gas pressure in the network
and/or adjust the solenoid valve accord-
ing to the instructions of this manual.
Air pressure switch opening.
The air pressure is too low, (the head is
bad adjusted).
The air pressure switch is faulty,
change it.
Burner shut down.
Gas pressure switch opening.
Check the pressure in the network and/or
adjust the solenoid valve according to the
instructions of this manual.