Configurations which can be modified by means of configuration software available at service centres are listed in the following
table.
FUNCTION
DESCRIPTION
DEFAULT
Operating mode
Selects one of five different operating modes
ON LINE
Output voltage
Selects the rated output voltage
(Phase - Neutral)
230V
Output nominal frequency
Selects the rated output frequency
50Hz
Autorestart
Waiting time for automatic power-on after the return of mains
voltage
5 sec.
Auto power off
Automatic UPS power-off in battery operation mode if the
charge is lower than 5%
Disabled
Buzzer Reduced
Selects the audible alarm operating mode
Reduced
EnergyShare off
Selects the auxiliary socket operating mode
Always connected
Timer
Programmed UPS power on/off (daily)
Disabled
Autonomy limitation
Maximum battery operation time
Disabled
Maximum load
Selects the user overload limit
Disabled
Bypass Synchronization speed
Selects the synchronisation speed of the inverter to the bypass
line
1 Hz/sec
External synchronization
Selects the source of synchronisation for the inverter output
From bypass line
External temperature
Activates reading of the external temperature probe
Disabled
Bypass mode
Selects the mode of use of the bypass line
Enabled /
High sensitivity